Saturday, April 19, 2008
Display problem ? Click HERE
Pressure Relief Valve (PRV) mounted on top of a liquid filled vessel exposing to external fire attack, there was a great discussion on the potential of two phase relief via the PSV.
According to API Std 521, Jan 2007, Fifth edition, section 5.15.3.3.,
Above statement is clearly supported by experiments quoted in Emergency Relief System Design Using DIERS Technology, chapter 1, section 7.2.
Above experiments have shown that
Assessing potential of two phase relief via PSV mounted on top of liquid filled vessel exposing to external fire attack, the characteristic of process fluid in the vessel shall be studied carefully.
Related Topic
According to API Std 521, Jan 2007, Fifth edition, section 5.15.3.3.,
Statement from API implies that sustainable two phase relief via PSV for a liquid filled vessel exposing to external fire attack is very unlikely and can be neglected, with the condition the fluid is non-foamy, non-reactive and not captured in narrow-flow passage like jacket vessel. Narrow-flow passage could be extended to PSV inlet pipe which is rather small and discourage vapor-liquid disengagement in the pipe.
The hydraulic-expansion equations given in 5.14.3 may be used to calculate the initial liquid relieving rate in a liquid-filled system when the liquid is still below its boiling point. However, this rate is valid for a very limited time, after which vapour generation becomes the determining contributor in the sizing of the pressure-relief device.
There is an interim time period between the liquid-expansion and the boiling-vapour relief during which it is necessary to relieve the mixtures of both phases simultaneously, either as flashing, bubble, slug, froth or mist flow until sufficient vapour space is available inside the vessel for phase separation. With the exception of foamy fluids, reactive systems and narrow-flow passages (such as vessel jackets), this mixed-phase condition is usually neglected during sizing and selecting of the pressure-relief device. The aforementioned exceptions are discussed further in 5.15.3.4. Experience as well as recent work in this area [53], [54], [55], [56] has shown that the time required to heat a typical system from the relief-device set pressure to the relieving conditions allows for the relief of any two-phase flow prior to reaching the relieving conditions. As such, full disengagement of the vapour is realized at the relieving conditions and the assumption of vapour-only venting is appropriate for relief device sizing.
Experience has shown there is minimal impact on the discharge system for the two-phase transition period. However, the user may consider the impact of transient two-phase flow on the design of the downstream systems.
If a pressure-relief device is located below the liquid level of a vessel exposed to fire conditions, the pressure relief device should be able to pass a volume of fluid equivalent to the volume of vapour generated by the fire.
Determination of the appropriate state of the fluid can be complicated. A typical conservative assumption is to use bubble point liquid.
[53] H. G. FISHER and H. S. FORREST, "Protection of Storage Tanks from Two-Phase Flow Due to Fire Exposure", Process Safety Progress, Volume 14, No. 3, July 1995, pp. 183-199
[54] H. S. FORREST, "Emergency Relief System Design for Fire Exposure with Consideration of Multiphase Flow", 1995 International Symposium on Runaway Reactions and Pressure Relief Design, ISBN 0-8169-0676-9, Published by American Institute of Chemical Engineers, pp. 604-630
[55] H. MOTT and B. SPARROW, "A Simple Relief Valve Rating/Sizing Method for Fire Relief from Liquid-filled Vessels", presentation to API RP-521 Subcommittee, September 30, 2002
[56] L. L. SIMPSON, "Fire Exposure of Liquid-Filled Vessels", paper D29-190-1 presented at the 29th DIERS Users Group Meeting, Las Vegas, NV, April 29-May 1, 2002
Above statement is clearly supported by experiments quoted in Emergency Relief System Design Using DIERS Technology, chapter 1, section 7.2.
A 2-inch diameter relief device (nozzle) was rapidly opened on a tank that was 95% filled with 550 gallons of city water at approximately 15O0C and under its own vapor pressure of about 58.5 psig. Approximately 28% of the tank contents vented by two-phase flow (See below image).
The experiment was repeated, except that 1000 ppm of a liquid household detergent were added. Approximately 96% of the tank contents vented by two-phase flow (See below image).
Above experiments have shown that
- For non-foamy liquid, two phase relief via PSV will occur in liquid filled vessel until liquid level drop below a a level where vapor liquid disengagement occur. Liquid swelling in the vessel is main factor contributor to two phase relief.
- For foamy liquid, two phase relief would occur in liquid filled vessel until almost all the liquid in the vessel is empty.
Assessing potential of two phase relief via PSV mounted on top of liquid filled vessel exposing to external fire attack, the characteristic of process fluid in the vessel shall be studied carefully.
Related Topic
- Extra Caution When Eliminating Overpressure by Fire Attacks
- Should we consider JET FIRE for Pressure Relief Valve (PSV) load determination ?
- Should we install Butterfly valve for Pressure Relief Valve (PSV) isolation ?
- Requirement of overpressure protection devices on system design to PIPING code
- Workbook for Chemical Reactor Relief System Sizing
- A must have book...Emergency Relief System Design Using DIERS Technology
Labels: Fire, Overpressure Protection, Pressure Relief Device
0 Comments:
Post a Comment
Let us know your opinion !!! You can use some HTML tags, such as <b>, <i>, <a>
Subscribe to Post Comments [Atom]
Home:
<< Home